The SSG Monitors are advanced early warning loss detection and prevention monitoring
systems designed specifically for fire suppression systems.
SenTech's SSG models are cost effective, self-contained monitors of halogenated
gases that activate an alarm at a preset concentration that is programmed by the user.
The Series includes single, four and eight zone models. SenTech's unique built in leak
wait period minimizes nuisance false alarms.
SenTech SSG monitors provide 24/7 protection.
The SSG systems are based on an advanced infrared technology that can detect
multiple gas types at concentration levels as low as one part per million (PPM).
The SSG Monitoring System reduces the risk of accidental suppression
agent discharges by continuously sampling the air for halogenated compounds.
In critical environments, Halon and FM-200 discharges occur more frequently by accident
than by fire. The primary cause of agent discharges is refrigerant leaks from
supporting air conditioning systems. By installing a SenTech SSG Monitoring System, this
costly scenario can be avoided. One SSG Monitoring System can sample up to 16 zones and
can be field programmed for various refrigerants and types of agents providing the earliest
warning leak detection available today.
The SSG Monitoring System can interface with existing suppression system
panels to automatically abort a Halon discharge due to a refrigerant leak, thus preventing
the costly replacement of agents, and minimizing risks of downtime associated with a Halon
system discharge.
SenTech's SSG Monitoring System is a cost effective solution for
preventing critical downtime, avoiding business disruptions and suppressing system equipment
failures.
Specifications
Sensitivity
As low as 1 PPM
Weight
32 lbs, (14.4 Kgs)
Power Requirements
120/240 Volt 50/60 Hz
Range
0 to 1000 PPM
Alarm Trip Points
Low Alarm 0 to 100% of Full Scale
Main Alarm 0 to 100% of Full Scale
High Alarm fixed at 100% of Full Scale
Operating Environmental Range
32o - 125o Fahrenheit
0o - 50o Celsius
Alarm Outputs
Indicator Light
3 Alarm Relays with 4 Form C contacts
(5 amps maximum each)
Options/Accessories
- Remote transmitters: Oxygen & Toxic Gases
- Remote PPM indicator w/ Audible silent switch
- Strobe light, horn, strobe/horn combination
- Zone pickup tubing